Project Description

Specifications

  • Weight: 5kg
  • Power supply rating: 3 Amps total including battery charge 28V +/- 2V
  • Fire relay contact rating: 2A /30VDC maximum for each
  • Number of detectors per zone: ≤30 PCS conventional detectors
  • Sounder circuit end of line: 10K±5% 1/2 Watt resistor

Description

The automatic extinguisher control panel is designed in accordance with European standards EN54-2 and EN54-4 Fire Detection and Fire Alarm systems – Control and Indicating Equipment and EN12094-1 Fixed firefighting systems – Components for gas extinguishing systems – Part 1: Requirements and test methods for electrical automatic control and delay devices. The control equipment is a combined fire alarm control panel and extinguishing system and has four detection zones, any or all of which are capable of contributing to the extinguishant release decision. Control panels have an integral, mains powered battery charger and power supply designed in accordance with the requirements of EN54-4.